Note :- Available in the Brands of Ge Tech, Omax.
|
| ABC Type dry Powder (Stored Pressure) |
| |
Suitable for A B C & E Class of Fire involving material like Paper, Wood, Cotton, Petrochemical Products, Paints, Resins, Pigment, Varnish, Gases in the compressed form like Oxygen, Acetylene, LPG & also for fires involving electrical equipment. |
| |
|
|
| CAPACITY IN KG. |
1/2 |
1 |
2 |
5 |
10 |
| IS SPECIFICATIONS NO. |
13849 |
13849 |
13849 |
13849 |
13849 |
| N2 GAS PRESSURE (kgf/cm2) |
18 |
18 |
18 |
18 |
18 |
| DIMENSION in MM APPX. HT./DIA. |
217x64 |
340x87 |
380x108 |
505x150 |
616x175 |
| WORKING PRESSURE AT 27±2°C (Kgf/cm2) |
14 |
14 |
14 |
14 |
14 |
| TESTING PRESSURE kgf/Cm2 |
30 |
30 |
30 |
30 |
30 |
| RANGE OF DISCHARGE (MTRS.) |
2-3 |
2-3 |
2-3 |
4-6 |
6-7 |
| DURATION OF DISCHARGE (SEC.) |
8-10 |
8-10 |
8-10 |
15-20 |
23-30 |
| SPECIAL FEATURES |
- |
 |
 |
 |
 |
................
|
Carbon-Di-Oxide Portable & Mobile |
| |
Suitable for B & C Class Of Fires involving materials like Petrochemical Products, Paints, Resins, Pigment, Varnish, Gases in the compressed form like Oxygen, Acetylene, LPG & CNG and also for fires involving electrical equipment. |
| |
|
|
|
| Dry Powder Fire Extinguisher |
| |
Suitable for B & C Class Of Fires involving materials like Petrochemical Products, Paints, Resins, Pigments, Varnishes, Gases in the compressed form like Oxygen, Acetylene, LPG & CNG & also for fires involving electrical equipment. |
| |
|
|
| CAPACITY in KG. |
5 |
10 |
25 |
50 |
75 |
| SPECIFICATIONS NO. |
2171 |
2171 |
10658 |
10658 |
10658 |
| OS2 GAS CARTRIDGE (GMS.) |
120 |
200 |
650 |
1650 |
2000 |
| DIMENSION (MM) (ht. x dia.) |
495x150 |
580x173 |
- |
- |
- |
| WORKING TEMP. RANGE °C |
27±2 |
27±2 |
27±2 |
27±2 |
27±2 |
| WORKING PRESSURE AT 27±°C (Kgf/cm2) |
14 |
14 |
14 |
14 |
14 |
| TESTING PRESSURE Kgf/Cm2 |
30 |
30 |
30 |
30 |
30 |
| JET LENGTH (METERS) |
4-6 |
4-6 |
6-7 |
8-9 |
10 |
| DISCHARGE TIME (SECOND) |
15-20 |
23-30 |
25-30 |
40-50 |
50-60 |
| SPECIAL FEATURES |
 |
 |
 |
 |
 |
................
|
| Water CO2 Type |
| |
| Suitable for A Class of fire involving materials like paper, wood and cotton. |
| |
|
|
| CAPACITY in Ltrs. |
9 |
50 |
9 (Stored Pressure) |
| IS SPECIFICATIONS NO. |
940 |
13385 |
6234 |
| CO2 GAS CARTRIDGE (GMS.) |
60 |
300 |
---- |
| DIMENSION (MM) (ht. x dia.) |
580x173 |
- |
580x173 |
| WORKING TEMP. RANGE °C |
27±2 |
27±2 |
27±2 |
| WORKING PRESSURE AT 27±2°C (Kgf/cm2) |
14 |
14 |
14 |
| TESTING PRESSURE Kgf/Cm2 |
30 |
30 |
25 |
| JET LENGTH (METERS) |
6-8 |
10-12 |
6-8 |
| DISCHARGE TIME (SECOND) |
60-80 |
150-180 |
60-80 |
| SPECIAL FEATURES |
 |
 |
- |
................
|
| Mechanical Foam (AFFF) |
| |
Suitable for A & B class for fires involving materials like Paper, Wood, Cotton, Petroleum products, paint, pigment & varnish. |
| |
|
|
| CAPACITY in Ltrs. |
9 |
50 |
9 (Stored Pressure) |
| IS SPECIFICATIONS NO. |
10204 |
13386 |
4989 |
| CO2 GAS CARTRIDGE (GMS.) |
60 |
300 |
- |
| DIMENSION (MM) (ht. x dia.) |
580x173 |
- |
580x173 |
| WORKING TEMP. RANGE °C |
27±2 |
27±2 |
27±2 |
| WORKING PRESSURE AT 27±2°C (Kgf/cm2) |
14 |
14 |
14 |
| TESTING PRESSURE Kgf/Cm2 |
30 |
30 |
25 |
| JET LENGTH (METERS) |
6-8 |
10-12 |
6-8 |
| DISCHARGE TIME (SECOND) |
25-30 |
90-120 |
25-30 |
| SPECIAL FEATURES |
|
|
- |
................
|
| |
| Carbon Dioxide Gas Cartridge For |
| |
|
| CAPACITY In Gms. |
60 |
120 |
200 |
300 |
| IS SPECIFICATIONS NO. |
4947 |
4947 |
4947 |
4947 |
| COMPLETE WT. EMPTY IN (GMS.) |
570 |
750 |
980 |
1240 |
| COMPLETE WT. CHARGED (GMS.) |
630 |
870 |
1180 |
1540 |
| WORKING PRESSURE AT 27±2°C (Kgf/cm2) |
140 |
140 |
140 |
140 |
| HYD. TESTING PRESSURE Kgf/Cm2 |
250 |
250 |
250 |
250 |
| DIA. OF PIPE (MM) |
45 |
51 |
51 |
51 |
| OVERALL HEIGHT (MM) |
151 |
181 |
245 |
350 |
| SPECIAL FEATURES |
|
|
|
- |
|
| |
| |